Cannon has the standardized VC-7 unit in stock and ready for shipment. This unit handles up to 1000lb/hr of vented steam, and up to 20GPM of cold water flow used to collapse the steam and capture the energy. The included chart shows the performance of this unit at various suggested flow rates.
REQUEST INFO BROCHURE DIAGRAM
VC - 7 OPERATING RANGE & PREDICTED PERFORMANCE |
Steam Flow From Vent (Pounds Per Hour) |
Water Flow (Gallons Per Minute) |
Expected Heat Recovery (BTU/Hr.*) |
24-Hour Days to Payback** |
200 |
3 |
190,000 |
128 |
300 |
4 |
285,000 |
85 |
400 |
6 |
380,000 |
64 |
500 |
7 |
475,000 |
51 |
750 |
10 |
712,500 |
34 |
1000 |
15 |
950,000 |
26 |
*Based on conditions as show. Will vary based on actual operating conditions
**Based on fuel cost of $6.50/MMBTU and boiler efficiency of 80% |
Unit Weight = 125 lb.
Shipping Weight = 140 lb.
|